9106A HART Transparent Repeater

9106A HART Transparent Repeater

Quick Overview

9106A is a 1- or 2-channel isolated 1:1 repeater. The device supplies 2-wire SMART transmitters and can also be used for 2-wire SMART current sources. HART & BRAIN protocols are supported and are transferred bi-directionally.
View Options

Details

Application

  • 9106A is a 1- or 2-channel isolated 1:1 repeater.
  • The device supplies 2-wire SMART transmitters and can also be used for 2-wire SMART current sources. HART & BRAIN protocols are supported and are transferred bi-directionally.
  • 9106A can be mounted in and receive signals from non-classified area or zone 2.
  • For duplication/migration purposes, the outputs can be sent to two different DCS/PLC/HMI or any monitoring system.
  • In safety applications (SIL loops), the 9106AxB can be used as a splitter with the following output configuration:
    · When using 9106AxB in a SIL2 safety function, channel 1 is used for the safety loop. Channel 2 can be used for any non-safety device.
    · For higher safety purposes (SIL 3), 9106AxB can be used as a splitter for SIL 3 loops. Channel 1 and 2 are then connected to the same safety PLC, where channel 2 is used as a redundant diagnostic channel. (For more information, consult the FMEDA Report and the Safety Manual).

 

Advanced features

  • The detachable display and the green and red front LEDs indicate operation status for each channel.
  • Monitoring of error events and cable breakage on input via the individual status relay and/or a collective electronic signal via the power rail.

 

Technical characteristics

  • High galvanic isolation of 2.6 kVAC.
  • Fast response time <5 ms
  • High accuracy better than 0.1%.
  • 2-wire transmitter supply >16 V.

 

Mounting

  • The devices can be mounted vertically or horizontally without distance between neighbouring units.

 

Environmental Conditions

Operating temperature -20°C to +60°C
Storage temperature -20°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & measurement / overvoltage cat. II

 

Mechanical specifications

Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501 / 4511 109 x 23.5 x 116 / 131 mm
Weight approx. 250 g
Weight incl. 4501 / 4511 (approx.) 265 g / 350 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.08 mm2 AWG 26...14 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6 : 2007
Vibration: 2...13.2 Hz ±1 mm
Vibration: 13.2...100 Hz ±0.7 g

 

Common specifications

Supply

Supply voltage 19.2...31.2 VDC

Isolation voltage

Test /working: Input to any 2.6 kVAC / 300 VAC reinforced isolation
Analog output to supply 2.6 kVAC / 300 VAC reinforced isolation
Status relay to supply 1.5 kVAC / 150 VAC reinforced isolation

Response time

Response time (0...90%, 100...10%) < 5 ms
Fuse 1.25 A SB / 250 VAC
Max. required power ≤ 1.1 W / ≤ 1.9 W (1 ch. / 2 ch.)
Max. power dissipation, 1 / 2 ch. ≤ 0.8 W / ≤ 1.2 W
SMART bi-directional communication
frequency range
0.5...7.5 kHz
Signal / noise ratio > 60 dB
Accuracy Better than 0.1% of selected range
mA, absolute accuracy ≤ ±16 μA
mA, temperature coefficient ≤ ±1.6 μA / °C
Effect of supply voltage change on output
(nom. 24 VDC)
< ±10 μA
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE 21,
A criterion, burst
< ±1% of span

 

Input specifications

Current input

Measurement range 3,5...23 mA
2-wire transmitter supply 9106A1x >16 V / 20 mA
2-wire transmitter supply 9106A2x >15 V / 20 mA
Sensor error detection: Loop break 4...20 mA < 1 mA
Input voltage drop, supplied unit < 4 V @ 23 mA
Input voltage drop, non-supplied unit < 6 V @ 23 mA

 

Output specifications

Current output

Signal range 3.5...23 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Current limit ≤ 28 mA

Status relay

Max. voltage 110 VDC / 125 VAC
Max. current 0.3 ADC / 0.5 AAC
Effect of external 2-wire supply
voltage variation
< 0.005% of span / V
Max. load resistance [Ω] (Vsupply - 3.5) / 0.023 A
Max. external 2-wire supply 26 VDC
Status relay output terminal 33-34: Relay function N.C.
Programmable low setpoint 0...29.9 mA
Programmable high setpoint 0...29.9 mA
Hysteresis for setpoints 0.1 mA
Max. voltage - hazardous installation 32 VDC / 32 VAC
Max. current - hazardous installation 1 ADC / 0.5 AAC
*of span = normal measurement range 4...20 mA

 

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
RoHS 2011/65/EU

 

Approvals

UL UL 61010-1
EAC TR-CU 020/2011
DNV-GL Marine Stand. f. Certific. No. 2.4
SIL SIL 2 / SIL3 certified & fully assessed acc. to IEC 61508

Availability: Stock Item

 

Components / Downloads

For further information, technical advice, or a quotation please call or email us. If you are not sure which product you need one of our technical sales advisors will be happy to discuss your application. We also accept company purchase orders by fax or post. Credit card orders can also be placed over the phone for any product.

REF DESCRIPTION DOWNLOADS PRICE ORDER ITEM
 
PR 9106A Transparent HART Repeater
9106A1A
9106A1A
Single channel isolated HART transparent repeater, 4-20mA input, 4…20 mA output, power supply 19.2 - 31.2, SIL2 certified to IEC 61508
View FileData Sheet
   Size: (369.18 KB)
£247.93
or call us for a quote
9106A1B
9106A1B
Dual channel isolated HART transparent repeater, 2 x 4-20mA input, 2 x 4…20 mA output, power supply 19.2 - 31.2, SIL2 certified to IEC 61508
£341.82
or call us for a quote
9106A2A
9106A2A
Single channel isolated HART transparent repeater, 4-20mA input, 4…20 mA output, power supply 19.2 - 31.2, Uo=25.6 V, SIL2 certified to IEC 61508
£251.10
or call us for a quote
9106A2B
9106A2B
Dual channel isolated HART transparent repeater, 2 x 4-20mA input, 2 x 4…20 mA output, power supply 19.2 - 31.2, Uo=25.6 V, SIL2 certified to IEC 61508
£351.32
or call us for a quote
 
Detachable Keypad / Display / Programmer
4510
4510

4510 Programming display for systems 4000 and 9000 devices. Each 4510 display can be used on several different units to allow for modification/transfer of operation parameters or on an individual unit as a fixed display for readout of process data and status. The 4510 display clicks onto the front of the units are is interchangeable between units for programming or display.

View FileDatasheet
   Size: (647.78 KB)
£69.00
or call us for a quote