Description
Features
- Analog and digital controller.
- 4 or 8 lines / 16 to 32 detectors max.
- Highly versatile controller
- Cost savings on wiring installations
Specifications
General Specifications
Dimensions (wall-mount): | 370 x 299 x 109 mm |
Dimensions (rack) | 482.8 x 177 x 192.5 mm |
Ingress protection | IP55 (wall-mount), IP31 (rack) |
Cable entries (wall-mount):
|
12 M16 cable glands, 4 to 8 mm² (8 to 11 AWG) outer diameter cable 6 M20 cable glands, 6 to 12 mm² (7 to 9 AWG) outer diameter cable |
Display:
|
LCD back-lit display + smart keys Display in video inverse in case of fault Customizable by user (display 1 to 16 channels simultaneously, fixed or scrolling, on events…) Bar graph with alarm threshold |
Visual indicators: | 7 LEDs per line, 1 LED fault indicator |
Buttons: | 5 smart keys, 1 audible alarm accept/reset button |
Operating Environment: | Temp: -20°C to +50°C, Humidity 5 – 95%RH |
Power Supply: | 100-240 vAC 50-60 Hz or 21-28 vDC, 112 W max |
Optional Battery: | Embedded back up power supply in option (0.6 Ah) |
Consumption: | 500 mA min (without module) |
Monitored Channels
Digital lines:
|
8 maximum RS-485 communication, proprietary protocol, 9600 Baud 2 twisted shielded-pair cable |
Analog channels:
|
8 maximum 0-23 mA analog signal input (4 to 20 mA reserved for measurement) 120 Ohm load resistance 2 or 3-core shielded cable |
Voltage (typical): | 21 to 28 vDC |
Max current output per line: | 500 mA |
Max current output in total: | 2.4 A permanent (3.2 A intermittently) |
Alarms
Per channel:
|
5 alarm levels (A1, A2, A3, Overscale, Underscale) + Fault Non-ambiguity reading option for combustible gases monitoring |
Programmable thresholds: |
On latest or averaged values, rising or falling alarms, manual or automatic acknowledgement |
On-board relays:
|
5 fully programmable alarm relays 1 fault relay (non-configurable) Dry contact relay DPCO relays with contact rating of 250 vAC, 2 A (inductive) |
Digital outputs: | RS-485 Modbus RTU serial link |