The PR 5450A is a head-mounted PROFIBUS PA temperature transmitter that connects industrial sensors to compatible digital process control systems. It accepts RTD, thermocouple, potentiometer, linear resistance and bipolar millivolt inputs, with single or true dual-input options. Designed for DIN form B sensor heads, it combines local signal conversion with network access to measurements, configuration and diagnostics.
The 5450A supports a wide range of temperature sensors and electrical inputs. This allows the same transmitter platform to be configured for different measurement points, from conventional temperature monitoring to resistance or low-level voltage measurement.
For suitable RTDs, Callendar–Van Dusen sensor matching allows individual sensor characteristics to be entered into the transmitter. Custom linearisation options provide further flexibility where the measurement requires a defined relationship between the input signal and the reported value.
True dual-input operation allows two compatible sensors to connect to one transmitter. Depending on the configuration, process data can include individual readings, an average or the difference between measurements. Minimum and maximum tracking provides further options for monitoring changing conditions.
Sensor redundancy supports applications where measurement continuity is important. Drift detection compares sensor readings and provides an alert when their difference exceeds a user-defined limit, helping identify a potential sensor problem before it becomes an obvious measurement failure.
Supporting PROFIBUS PA Profile 4.0, the 5450A transmits digital measurement values and status information to a compatible control system. Power and communication share the two-wire fieldbus connection.
The transmitter can also form part of an asset-management system, making device information and diagnostics available alongside process measurements. Configuration takes place through fieldbus communication using compatible software and the appropriate device integration files.
The 5450A provides diagnostic information aligned with NAMUR NE107, helping the receiving system distinguish device conditions that require attention. Programmable input limits and runtime metering support monitoring of sensor operating conditions.
Galvanic isolation separates the sensor inputs from the fieldbus circuit, with a specified isolation test voltage of 2.5 kVAC. This electrical separation helps manage potential differences between the measurement point and the connected system.
The compact circular housing fits compatible DIN form B sensor heads. The 5450A is suitable for general industrial installations and permitted Zone 2/22 applications, subject to the relevant approval and installation conditions.
When selecting the transmitter, confirm the sensor type, wiring arrangement, input combination and required measurement functions. The fieldbus supply, system integration files and enclosure must also suit the installation. For applications requiring a different hazardous-area protection level, consider the appropriately approved 5450B or 5450D version.
| Type | Version | Inputs |
| 5450 | A: Zone 2 and zone 22 / Class I, Division 2, Groups A, B, C, D. B: Zone 0, 1, 2 and zone 21, 22 including M1. D: Zone 0, 1, 2 and zone 21, 22 including M1 / Class I, Division 1, Groups A, B, C, D. | 1: Single Input (4 Terminals) 2: Dual Input (7 Terminals) |
Applications
Frequently Asked Questions
PR 5450A1 2-Wire Programmable Profibus PA Transmitters. Single Channel Input: -800 to 800mV or -0.1 to +1.7V; RTD (2, 3 or 4 Wire) Range -200 to +850°C; Thermocouples (Type B, E, J, K, L, N, R, S, T, U, W3, W5, Lr); Linear Resistance – 0 to 100kΩ or Potentiometer 10 to 100kΩ. Output: Profibus PA. Accuracy ≤±0.05% of span. Response Time: 75ms. Power Supply 7.5-48vDC @ <352mW. 1.5kVAC Galvanic Isolation. Namur NE21, NE44, NE89 and NE107. Approvals: Zone 2, (ATEX, IECEx & INMETRO); Zone 2 – Div 2 (CSA, FM); NEPSI & EAC Certification; SIL 2/3 Full Assessment IEC 61508. Operating Temp: -40 to +85°C.
PR 5450A2 2-Wire Programmable Profibus PA Transmitters. True Dual Channel Inputs: -800 to 800mV or -0.1 to +1.7V; RTD (2, 3 or 4 Wire) Range -200 to +850°C; Thermocouples (Type B, E, J, K, L, N, R, S, T, U, W3, W5, Lr); Linear Resistance – 0 to 100kΩ or Potentiometer 10 to 100kΩ. Output: Profibus PA. Accuracy ≤±0.05% of span. Response Time: 75ms. Power Supply 7.5-48vDC @ <352mW. 1.5kVAC Galvanic Isolation. Namur NE21, NE44, NE89 and NE107. Approvals: Zone 2, (ATEX, IECEx & INMETRO); Zone 2 – Div 2 (CSA, FM); NEPSI & EAC Certification; SIL 2/3 Full Assessment IEC 61508. Operating Temp: -40 to +85°C.
USB Loop Link programming kit to configure PR Electronics 5000 & 6000 Series devices. Loop Link 5909 consists of a communication box with USB cable to the PC, necessary cables for connection to the devices, a CD-ROM with the configuration program PReset and an installation manual. The communication box is powered by the USB port of the PC.
A real person will answer the phone and deal with your enquiry.
You can also click the button below and fill in our online enquiry form.
Need help with your products or have a question for us on our custom systems? Use the form below to send us a message and our experts will be in touch to help.