Description
Connect directly to any data logger input channel; no external power required.
- Rugged polyamide DIN mount case.
- Designed for industrial environments
- Self powered.
| Specifications – PACE AC Voltage Sensors | |
| Frequency Range | SV300: 48 – 400 Hz SV600: 48 – 65 Hz | 
| Voltage Overload | Full scale rating | 
| Accuracy (50 – 60 Hz) | ±0.25% of F.S. (includes effects of linearity 10% to 100% of F.S.) | 
| SV300 Only: Accuracy @ 400Hz | ±0.50%FS (includes effects of linearity 10% to 100% of F.S.) | 
| Temperature Effect | ±1.0% (-20 to 65°C) | 
| Output Ripple | Less than 1% full scale | 
| Response Time (99%) | 400 milliseconds | 
| Connections | Recessed screw terminals for input and output wiring | 
| Burden | 2.0 VA | 
| Size | 3.7″H x 3.1″W x 1″D | 
IMPORTANT: The AC Voltage Sensors must be mounted in a suitable panel or enclosure and the input & output terminals must be wired. A suitable ABS enclosure is available for either the SV300 or SV600.
WARNING: SHOCK OR INJURY HAZARD: Disconnect AC Power Source before wiring AC Sensor inputs.
TheSV600 Sensor includes an external potential transformer which also must be mounted and wired in a suitable panel or enclosure. External transformer size: 1.6″H x 2.8″W x 2″D.
Use the SV300 to monitor and record 24, 120 and 240 Vac circuits; use the SV600 to monitor and record 24, 120, 240 and 480 Vac circuits.
| Part No | Range (Frequency) | 
| SV300 | 0-300vAC (48 – 400 Hz) | 
| SV600 | 0-600vAC (48 – 65 Hz) | 
For a more flexible AC voltage sensor, try the DIN Rail Mounted AC Voltage Transducer
 
				