The PR 5335A is a head-mounted 2-wire transmitter that combines flexible sensor inputs with a 4-20 mA output and HART 5 communication. It accepts supported RTDs, thermocouples, linear resistance and bipolar millivolt signals, providing a configurable connection between field sensors and industrial monitoring or control systems. Its compact housing fits compatible DIN form B sensor heads.
The 5335A supports linearised temperature measurement with platinum and nickel RTDs, including PT100 and PT1000, alongside supported thermocouple types. RTD and resistance inputs accommodate two-, three- and four-wire sensor connections, with cable compensation appropriate to the selected arrangement.
It also converts linear resistance changes and bipolar millivolt signals into a standard current output, allowing suitable resistive sensors and low-level voltage sources to connect to receiving equipment.
Compatible two-sensor arrangements allow the transmitter to calculate a temperature difference or average. Differential measurement can compare two locations, while averaging combines the readings into a single reported value.
The sensor types, wiring arrangement and configured function must match the intended measurement. These functions provide alternatives to straightforward individual sensor measurement.
HART communication provides digital access over the same two-wire connection used for power and the current output. In conventional point-to-point operation, the 4-20 mA signal represents the configured process value while compatible HART equipment accesses additional digital information and settings.
This allows configuration and measurement access through the loop, supporting commissioning and maintenance without a separate communication cable to the transmitter.
The 5335A can be configured through compatible HART equipment or using PR Electronics PReset software with a suitable Loop Link interface. Settings are matched to the sensor, measurement range and required output behaviour.
Programmable sensor error indication provides a defined output response when a sensor fault is detected. Receiving equipment can use this response to distinguish a measurement problem from a normal process reading.
The loop-powered design uses two wires for both supply and output. Before installation, confirm the sensor connections, available loop voltage and receiving equipment requirements.
The 5335A suits general industrial installations and permitted Zone 2/22 applications under its certification conditions. Where an intrinsically safe installation requires the approval coverage of the 5335D, select that version and check the complete circuit against its installation requirements.
| Type | Version |
| 5335 | A: General Purpose, Zone 2, Div 2 D: Zone 0, 1, 2, 21, 22, M1/Div 1, Div 2 |
Applications
Frequently Asked Questions
PR 5335A 2-Wire Programmable Transmitters with HART 5 Protocol. Inputs: -800 to 800mV; RTD (2, 3 or 4 Wire) Range -200 to +850°C; Thermocouples (Type B, E, J, K, L, N, R, S, T, U, W3, W5, Lr); Linear Resistance – 0 to 7000Ω. Output: 4-20mA & HART 5 Protocol. Accuracy ≤±0.05% of span. Response Time: 1 to 60 Seconds. Power Supply 8-35vDC @ 0.8W Max. 1.5kVAC Galvanic Isolation. Namur NE21, NE43 and NE89. Approvals: Zone 2, (ATEX, IECEx & INMETRO); Zone 2 – Div 2 (CSA); DNV & EAC Certification; SIL Hardware Assessment. Operating Temp: -40 to +85°C.
USB Loop Link programming kit to configure PR Electronics 5000 & 6000 Series devices. Loop Link 5909 consists of a communication box with USB cable to the PC, necessary cables for connection to the devices, a CD-ROM with the configuration program PReset and an installation manual. The communication box is powered by the USB port of the PC.
A real person will answer the phone and deal with your enquiry.
You can also click the button below and fill in our online enquiry form.
Need help with your products or have a question for us on our custom systems? Use the form below to send us a message and our experts will be in touch to help.