DPT-R8 Differential Pressure Transmitter

The DPT-R8 is an electronic differential pressure transmitter with eight jumper selectable measurement ranges in one device, from +/-100PA up to 0-7000Pa. The output is selectable as 4-20mA or 0-10V. The units also have the option of an LCD or Auto Zero function.

Need help finding the right product?

Downloads

DPT2500-R8 Differential Pressure Transmitter

Description

 

Applications

 

  • Monitoring air filters, ventilators and blowers
  • Monitoring and control of air flows
  • Fan and blower control
  • Valve and flap control
  • Flow meter applications
  • Pressure monitoring and control in clean rooms

Specification

Accuracy ±1,5% or (±6Pa <250 Pa)
(including: general accuracy, temperature drift, linearity, hysteresis and repetition error)
Response Time 0.8 / 4 s selectable by push button
Suitable Media Air and non-aggressive gases
Measuring Element Piezoresistive
Power Supply 24 VAC or VDC ± 10%
Power consumption < 1.0 W (<1.5W with Iout 20mA)
Output Signal 0…10 VDC, Load R minimum 1kohm or
4…20 mA, maximum load 500 ohms
Operating Temperature -10…+50°C (-5…+50°C for –AZ model)
Housing IP 54 ABS housing with PC Cover.
Dimensions 90,0 x 71,5 x 36,0 mm

 

The standard device includes

  • Output signal 0-10 V and 4-20 mA in the same device
  • Adjustable response time

Available options

  • Autozero function
  • Display
    – the device is available with or without a display
    – it is also possible to order and install the display afterwards 

Selectable Pressure Ranges

Model 2500 Model 7000
-100 to +100 Pa 0 to 1000 Pa
0 to 100 Pa 0 to 1500 Pa
0 to 250 Pa 0 to 2000 Pa
0 to 500 Pa 0 to 2500 Pa
0 to 1000 Pa 0 to 3000 Pa
0 to 1500 Pa 0 to 4000 Pa
0 to 2000 Pa 0 to 5000 Pa
0 to 2500 Pa 0 to 7000 Pa


Auto Zero Element

The optional auto zero element allows the transmitter to perform as a maintenance free unit. The element automatically adjusts the transmitters zero point from time to time, this eliminates the zero point long term drift of the piezoresistive sensing element. Units without an Auto Zero Element will require a manual zeroing at least every 12 months.

Product

Ref

Price

Product Description

DPT2500-R8

£91.80

DPT-R8 Multi-Range Differential Pressure Transmitters for Air Pressure. 8 Jumper selectable ranges: ±100, 0-100, 0-250, 0-500, 0-1000, 0-1500, 0-2000, 0-2500 Pa. Selectable output of 4-20mA or 0-10vDC, Accuracy 1% ±2Pa < 125Pa (1% ±1Pa >125 Pa). Power Supply: 24vDC, ±10%. ABS Enclosure with IP54 Rating. Dimensions: 90 x 95 x 36mm. Operating Temperature -20 to + 50°C, 0-95%RH.

DPT2500-R8-D

£103.28

DPT-R8 Multi-Range Differential Pressure Transmitters for Air Pressure. 8 Jumper selectable ranges: ±100, 0-100, 0-250, 0-500, 0-1000, 0-1500, 0-2000, 0-2500 Pa. Selectable output of 4-20mA or 0-10vDC, Accuracy 1% ±2Pa < 125Pa (1% ±1Pa >125 Pa). Power Supply: 24vDC, ±10%. Back-lit LCD with measurement and units. ABS Enclosure with IP54 Rating. Dimensions: 90 x 95 x 36mm. Operating Temperature -20 to + 50°C, 0-95%RH.

DFK

£4.84

Duct Fixing Kit (DFK). Kit includes 2m of 6mm i/d plastic tubing, 2 x pitot tubes and 4 fixing screws.