Description
The PS600 is intended for use in commercial environments. It is designed with field selectable set points from as low as 40 Pa to as high as 600 Pa. The NO/NC switch has a 3A Resistive Load limit, which can be used for space heaters or lighting control. The lower 2A Inductive Load limit is more suited for use with coils, pumps, fans or solenoids. Alternatively, you can always connect through an external relay with a higher rating.
Applications
- VAV Box Monitoring: Variable Air Volume boxes move a lot of air through narrow ducts. These higher ranges monitor the pressure inside the duct to ensure the dampers are modulating correctly.
- Industrial Cooling Fans: Monitoring large intake fans for data centers or electrical rooms where the air resistance is much higher than a standard office building.
Specifications
| Measurement Range: | 40 to 600 Pa |
| Measuring Units: | Pascals |
| Accuracy: | ±8 Pa (Low Limit), ±15% (High Limit) |
| Overpressure: | 25kPa Proof Pressure (50kPa Burst Pressure) |
| Electrical Connection: | 3 Screw Terminal |
| Switching Output: | 24-250vAC, 3A Max (2A Inductive Load) |
| NO/NC Contact | |
| Cable Entry: | M16 Gland |
| Pressure Fittings: | 5mm Diameter Males Ports, ABS with Silicone Membrane |
| Operating Conditions: | -20 to +60°C, 0-95%RH (Non-Condensing) |
| Materials: | ABS housing with PC Cover |
| Dimensions Housing: | 105.0 x 73.0 x 63.0mm |
| Weight: | 150g |
| Protection: | IP54 |