Description
Features
- 
- Universal input will accept:
 – Thermocouples: Thermocouple (Types J, K, T, N, R, S, B, E)
 – RTD (PT100’s)
 – 0-20mA or 4-20mA
 – 0-50mV
 Â Â – 0-5V or 0-10V.
- Precision:
 – Thermocouples J, K, T, E: 0.25 % of the span 1ºC
 – Thermocouples N, R, S, B: 0.25 % of the span 3ºC
 – PT100: 0.2 % of  the span
 – 4-20 mA, 0-50 mV, 0-5 V, 0-10 V: 0.2 % of the span
- Input adjustable Offset allows small indication corrections
 
- Analog input signal retransmission over 0-20 mA or 4-20 mA
- Up to 2 programmable alarms outputs
- Up to 2 relay outputs, SPDT and SPST-NO
- Alarm Functions: minimum, maximum, differential, minimum differential, maximum differential and sensor break
 
- Universal input will accept:
- 
- Features Initial alarm blocking function
 
- 
- Flash alarm function alerts operator to condition while in alarm state
 
- Sensor failure detection
- Password parameter protection
- Factory calibration parameters recovery
- Universal switching power supply ensures high precision even under mains voltage oscilations
- Optional auxiliary 24vDC power supply to connect field transmitters
- Optional RS485 interface
- Power Supply:
 – 100 to 240 vAC (±10 %), 50/60 Hz
 – 48 to 240 vDC (±10 %)
 – 24 to 240 vDC (±10 %) (Basic model only)
- Dimensions: 48 x 48 x 80 mm
- Internal Resolution: 32767 levels (15 bits)
- Display Resolution: 12000 levels (de -1999 to 9999)
- Input reading rate: up to 55 per second
- Certifications: CE, UL
 
				
 
								 
								 
								 
								