omni instruments | sensors and data acquisition equipment

Sales & Technical Support

Edit Content

CTX300 Gas Detector for Non-Hazardous Areas

The CTX300 gas detector is designed with a robust polycarbonate housing for gas detection in safe areas of Oxygen, Carbon Dioxide, Toxic and refrigerant gases. The polycarbonate housing is very durable and is not affected by harsh environments. The CTX 300 comes equipped with pre-calibrated sensor units and allows for maintenance by a single person. Units provide a 4-20mA output for the gas levels detected and an optional display can be incorporated.

Need help finding the right product?

Downloads

CTX300 Gas Detector

Description

Features

  • 4-20mA output analog transmitter with optional backlit display
  • Plug-in and pre-calibrated sensors
  • Available with electrochemical, infrared or semi-conductor sensors
  • Detection of O2, CO2, toxic and refrigerant gases
  • More than 30 different sensors are available for detection of most toxic gases in the industry
  • Available in an infrared version for CO2
  • Suitable for commercial or industrial applications in unclassified areas

Specifications

Power Supply: 15-32vDC
Output: 4-20mA
Display: Optional Back-lit display
Housing: IP66 Polycarbonate
Dimensions: 130 x 136 x 69mm
Operating Temperature: -20 to 50°C

Sensors Available

Electrochemical Sensors:

 

O2, CO, H2S, NO, NO2, SO2, Cl2, H2, HCl, HCN, NH3, ETO/PO, HF, O3, PH3, ClO2 and COCl2.
Infrared Sensors: CO2.
Semi-Conductor Sensors
(Solvents):
Methylene Chloride, Methyl Chloride, Toulene, Trichlorethylene, Xylene and Ethanol.
Semi-Conductor Sensors
(Refrigerants): 
R12, R22, R123, R134A, R142B, R11, R23, R141B, R143A, R404A, R507, R410A and R32.

All the above gases can be detected by the CTX300. The product builder below covers the most common options available. CO2 and other specialist versions are available in the product list further down and the remaining refrigerant and solvent versions are available on request.

Product

Ref

Price

Product Description

WC3AO2F

£775.00

CTX 300 Fixed Gas Detector with Integrated Display. Electrochemical Oxygen (O2) Cell, Range 0-30%. Accuracy ±1.5% (% at PA full scale), response time less than 10 seconds. Operating temperature -20 to +50°C. Life span 24 months.

WC3AO2G

£935.00

CTX 300 Fixed Gas Detector with Integrated Display. Electrochemical Oxygen (O2) Cell, Range 0-30%. Accuracy ±1.5% (% at PA full scale), response time less than 10 seconds. Operating temperature -20 to +50°C. Life span 60 months.

WC3AO2S

£985.00

CTX 300 Fixed Gas Detector with Display. Electrochemical Oxygen (O2) Cell, Range 0-100%. Accuracy ±1.5% (% at PA full scale), response time less than 20 seconds. Operating temperature +5 to +40°C. Life span 36 months

WC30CO2A

£615.00

CTX 300 Fixed Gas Detector. Infrared Carbon Dioxide (CO2) Cell, Range 0-5000ppm (0.5%). Accuracy ±2% (% at PA full scale), response time less than 20 seconds. Operating temperature -40 to +50°C. Life span 60 months.

WC30CO2B

£615.00

CTX 300 Fixed Gas Detector. Infrared Carbon Dioxide (CO2) Cell, Range 0-5%. Accuracy ±2% (% at PA full scale), response time less than 20 seconds. Operating temperature -40 to +50°C. Life span 60 months.

We are here to help

Need help with your products or have a question for us on our custom systems? Use the form below to send us a message and our experts will be in touch to help.