Description
Advanced features
- Configuration and monitoring by way of detachable display front (PR 4501).
- Selection of direct or inverted function for each channel via PR 4501.
- Advanced monitoring of internal communication and stored data.
- Optional redundant supply via power rail and/ or separate supply.
- SIL 2 functionality is optional and must be activated in a menu point.
Application
- 9202B can be mounted in the safe area or in zone 2 / Cl. 1 div. 2 and receive signals from zone 0, 1, 2 and zone 20, 21, 22 including mining / Class I/II/III, Div. 1, Gr. A-G.
- Pulse isolator for transmission of signals to the safe area from NAMUR sensors and mechanical switches installed in the hazardous area.
- Monitoring of error events and cable breakage via the individual status relay and/or a collective electronic signal via the power rail.
- The 9202B has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
Technical characteristics
- 1 green and 2 yellow/red front LEDs indicate operation status and malfunction.
- 2.6 kVAC galvanic isolation between input, output and supply.
Mounting
- The devices can be mounted vertically or horizontally without distance between neighbouring units.
Environmental Conditions
Specifications range | -20°C to +60°C |
Storage temperature | -20°C to +85°C |
Calibration temperature | 20…28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Installation in | Pollution degree 2 & measurement / overvoltage cat. II |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Dimensions (HxWxD) w/ 4501 / 4511 | 109 x 23.5 x 116 / 131 mm |
Weight approx. | 170 g |
Weight incl. 4501 / 4511 (approx.) | 185 g / 270 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13…2.08 mm2Â AWG 26…14 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 : 2007 |
Vibration: 2…13.2 Hz | ±1 mm |
Vibration: 13.2…100 Hz | ±0.7 g |
Common specifications
Supply |
|
Supply voltage | 19.2…31.2 VDC |
Isolation voltage |
|
Test /working: Input to any | 2.6 kVAC / 300 VAC reinforced isolation |
Analog output to supply | 2.6 kVAC / 300 VAC reinforced isolation |
Output 1 to output 2 | 1.5 kVAC / 150 VAC reinforced isolation |
Status relay to supply | 1.5 kVAC / 150 VAC reinforced isolation |
Auxiliary supplies |
|
NAMUR supply | 8 VDC / 8 mA |
Fuse | 400 mA SB / 250 VAC |
Max. required power | ≤ 3 W (2 channels) |
Programming | Communication enabler 4511 / Programming front 4501 |
Response time for cable fault | < 200 ms |
Input specifications
Sensor types | NAMUR according to EN 60947-5-6 / mechanical contact |
Frequency range | 0…5 kHz |
Min. pulse length | > 0.1 ms |
Input resistance | Nom. 1 kΩ |
Trig level, signal | < 1.2 mA, > 2.1 mA |
Trig level, cable fault | < 0.1 mA, > 6.5 mA |
Output specifications
Relay output |
|
Max. switching frequency | 20 Hz |
Max. voltage | 250 VAC / 30 VDC |
Max. current | 2 AAC / 2 ADC |
Max. AC power | 500 VA / 60 W |
Status relay |
|
Max. voltage | 110 VDC / 125 VAC |
Max. current | 0.3 ADC / 0.5 AAC |
Max. AC power | 62.5 VA / 32 W |
NPN outputs |
|
Max. switching frequency | 5 kHz |
Min. pulse length | > 0.1 ms |
Max. load, current / voltage | 80 mA / 30 VDC |
Voltage drop at 80 mA | < 2.5 VDC |
Observed authority requirements
EMC | 2014/30/EU |
LVD | 2014/35/EU |
Approvals
ATEX 2014/34/EU | KEMA 07ATEX0146 X |
IECEx | KEM 06.0039X |
FM | 3034430-C |
INMETRO | NCC 12.1307 X |
UL | UL 61010-1 |
EAC | TR-CU 020/2011 |
EAC Ex TR-CU 012/2011 | RU C-DK.GB08.V.00410 |
CCOE | P337349/5 |
DNV-GL Marine | Stand. f. Certific. No. 2.4 |
SIL | SIL 2 certified & fully assessed acc. to IEC 61508 |