Description
Applications
The 3100 series is ideal for the conversion and/or isolation of inputs from K & J Type Thermocouples plus 2-, 3- or 4-wire PT100 temperature sensors into 4-20mA outputs. All units are suitable for installation in Hazardous Zone 2 areas, including power rails and control units.
Features
- Rational DIP-switch setting
- Signal conditioning which ensures that no re-calibration is required after DIP-switch programming.
- 3113 unit provide a 4-20mA output with an embedded HART 7 protocol
- Reliable watchdogs LED indicates an error in the setup, hardware or power supply.
- Unique protection against wiring errors
- Effective isolation to EN 61010-1 and EN 61140
- Easy mounting / dismounting
- Space-saving design. At only 6 mm wide and can be mounted next to
each other, permitting up to 330 channels per metre. - Flexible supply voltage 24 VDC ±30%.
- The devices are vibration-tested via DNV and GL approvals and can be retained on the rail with the 9403 module stop.
- 9400 Power Rail and 3405 Power Connector unit will provide power to up to 100 units with up to 2.5A.
- 3405 Power Connector unit can provide a power supply to sensors from the Power Rail.
- All units are suitable for ATEX Zone 2 Environments
Specifications
Product Code | Description | Input | Output | Program Using |
3101 | TC Converter | K & J Type Thermocouples | mA or V | DIP-Switches |
3102 | PT100 Converter | 2-, 3-, or 4-wire PT100 | mA or V | DIP-Switches |
3111 | TC Converter/Isolator | K & J Type Thermocouples | Isolated mA or V | DIP-Switches |
3112 | PT100 Converter/Isolator | 2-, 3-, or 4-wire PT100 | Isolated mA or V | DIP-Switches |
3113
|
HART Temperature Converter | 2-, 3-, or 4-wire PT100, K & J Type Thermocouples |
Isolated Active 4-20mA with HART 7 Protocol | DIP-Switches, plus HART 7 revision protocol for extended programming |
Power Supply Options
The 3100 Slim Series units can be supplied in various different ways:-
- One unit can be connected to suitable 24vDC ±30% power supply and then looped to up to 130 additional units, max 2.5A.
- One unit can be connected to a suitable 24vDC ±30% power supply and mounted on to the 9400 Power Rail to distribute power to up to 20 units, max 0.4A
- The 3405 Power Connector Unit can be connected to a suitable 24vDC ±30% power supply and then to the 9400 Power Rail to distributor power to up to 100 units, max 2.5A.
- The 9410 Power Connector Unit can be connected to a suitable 24vDC ±30% power supply (plus a secondary back-up power supply) and then to the 9400 Power Rail to distributor power to up to 200 units, max 4A.
- Loop-powered units are powered directly from the 4-20mA signal.
All devices are ATEX Approved and can safely be used in a safe area, or in ATEX Zone 2 environments.