Description
Features
- IR3 Flame detector
- Long distance flame detection (up to 140ft/43m)
- Highly Immune to False Alarms
- Large Field of View (100° horizontal and 90° vertical)
- wo output options Alarm and Fault Relays or a stepped mA ouptut
- RS485 Modbus compatiblity
- Automatic and Manual Built-In-Test (BIT)
- 3-Year Warranty
Applications
- Airport Terminals
- Archives
- Banks and Office Buildings
- Cable Tunnels
- Car Parks and Garages
- Historical and Cultural Site
- Hospitals
- Public Buildings
- Shopping Centres
- Storage Areas
- Train Station and Terminals
Specification
Spectral Response | Three IR Bands | |||||
Detection Range (Highest Sensitivity Setting for 1ft² (0.1m²) pan fire) |
Gasoline n-Heptane Diesel Fuel JP5 Kerosene Alcohol (Ethanol) |
Ft 140 140 100 100 100 100 |
M 43 43 30 30 30 30 |
IPA (Isopropyl Alcohol) Methanol Methane LPG (Propane) Polypropylene Pellets Office Paper |
Ft 115 100 40 40 50 50 |
M 35 30 12 12 15 15 |
Response Time | Typical 5 Seconds | |||||
Adjustable Time Delay | Up to 30 Seconds | |||||
Sensitive Range | 4 Sensitive Ranges for 1ft² (0.1m²) gasoline pan fire: 35ft (11m) up to 140ft (43m) | |||||
Field of View | 100° horizontal, 90° vertical | |||||
Built-in Test | Manual and Automatic BiT | |||||
Temperature Range | Operating: -40 to 70°C (-40 to 160F) Storage: -40 to 70°C (-40 to 160F) |
|||||
Power Supply | 18-32vDC | |||||
Power Consumption | 20/20MPI-R @ 24vDC: Max 15mA in Stand-by. 25mA in Alarm. 20/20MPI-M @ 24vDC: Max 16mA in Stand-by. 36mA in Alarm. |
|||||
Enclosure | Polycarbonate | |||||
Dimensions | 119 x 119 x 74mm |