Description
Features
- Single channel gas controller
- Available pre-configured for use with O2, CO, CO2, CH4, H2 and LPG 4-20mA gas detectors.
- Easy Duo Version includes MX16 Controller and OLCT10N detector with 5m of cable.
- Low Cost and Easy to Install
- Integrated Relays
- RS485 Output Signal Option.
- Easy to read large graphic and multi-language LCD back-lit display
- Soft-touch Keys for Embedded Menus
Applications
- Lack of Oxygen in MRI Rooms
- Excess CO2 in Breweries or Cellars
- Gas Leaks in Small Boiler Rooms
- Gas Releases in Battery Charging Areas
- Water Water Treatment Plants
- Petrochemical
- Laboratories
Specifications
General Specifications
Dimensions: | 265 x 266 x 96mm |
Ingress protection | IP55 |
Cable entries:
|
3 M16 cable glands, 4 to 8 mm² (8 to 11 AWG) outer diameter cable 2 M20 cable glands, 6 to 12 mm² (7 to 9 AWG) outer diameter cable |
Display:
|
LCD back-lit display + smart keys Display in grayscale in case of fault Bar graph with alarm threshold |
Visual indicators: | 6 LEDs, 5 LEDs for Detector Status Line, 1 LED fault indicator and 1 LED Power Condition |
Buttons: | 5 smart keys, 1 audible alarm accept/reset button |
Operating Environment: | Temp: -20°C to +50°C, Humidity 5 – 95%RH |
Power Supply: | 100-240vAC 50-60 Hz (35W) |
Consumption: | 250 mA max (without captor) |
Monitored Channels
Digital lines:
|
RS-485 communication, proprietary protocol, 9600 Baud 2 twisted shielded-pair cable |
Analog channels:
|
1 x 4-20mA 0-23 mA analog signal input (4 to 20 mA reserved for measurement) 120 Ohm load resistance 2 or 3-core shielded cable |
Max current output per line: | 0.42 to 1A with internal AC power |
Alarms
Per channel: |
2 alarm levels (Al1, AL2) + negative drift fault |
Accessible and modifiable alarm threshold Al1 and Al2, manual acknowledgement | |
On-board relays:
|
2 alarm relays 1 fault relay (non-configurable) Dry Contact Relay, RCT, 250vAC, 5A |
Digital outputs: | RS-485 Modbus RTU Comms |
The Easy Duo option for the MX 16 controller includes a OLCT 10N detector for O2 or CO2 version with a 10 metre cable included (specific RS485 for digital communication). Factory preconfigured, it doesn’t require configuration software.