The PR 4179B monitors AC current or voltage and provides two configurable relay outputs for alarm and control duties. Inputs up to 5 A RMS or 300 V RMS suit current transformer monitoring and supply voltage supervision, with selectable ranges to match the installation.
Separate switching points allow warning and trip signals from one measurement. High, low and window functions detect departures from the required operating range, while adjustable hysteresis and time delays help prevent nuisance switching.
An optional PR 4500 series interface provides configuration, live readings and diagnostics. Choose the 4510 for local display and programming, the 4511 for Modbus communication or the 4512 for Bluetooth access. Password protection helps control configuration changes, and process simulation supports commissioning checks.
The compact housing mounts on standard 35 mm DIN rail and accepts supplies of 21.6–253 V AC or 19.2–300 V DC. Galvanic isolation, tested at 2.3 kV AC, separates the measurement and control circuits. Front LEDs indicate power and relay status, providing a quick visual check during operation.
Applications
Frequently Asked Questions
[Omni FAQ Notification] Linked to Product ID 197009 successfully, but the field _omni_geo_faq contains no data.
PR 4179B Programmable Universal Trip Amplifier with universal AC or DC power supply. Input: 0-5A AC RMS or 0-300vAC RMS. Relay Outputs: Setpoint, Window, Error Indication, Latch, Power and Off. 2.3kVAC isolation voltage. Power supply 21.6 – 253vAC or 19.2 – 300vDC. DIN Rail mounted. Dimensions: 109 x 23.5 x 104mm. Operating Temperature -20 to +60°C, 0-95%RH (non-condensing).
PR 4510 Programming display for systems 4000 and 9000 devices. Each 4510 display can be used on several different units to allow for modification/transfer of operation parameters or on an individual unit as a fixed display for readout of process data and status. The 4510 display clicks onto the front of the units are is interchangeable between units for programming or display.
PR 4511 Programming display and Modbus RTU protocol interface for systems 4000 and 9000 devices. Each 4511 display can be used on several different units to allow for modification/transfer of operation parameters or on an individual unit as a fixed display for readout of process data and status, plus as an RS485 Modbus RTU connection to a local network. The 4511 display clicks onto the front of the device and an RJ45 connector on top of the unit allows for connection to a Modbus network.
PR 4512 Bluetooth Communications Interface. Allows for programming and live readings to a iOS or Android device and any of the 4000 and 9000 Series devices. Each 4512 display can be used on several different units to allow for modification/transfer of operation parameters or on an individual unit as a fixed display for readout of process data and status, plus as the 4512 can also provide 30 days data logging at 1 second intervals of the connected devices. The 4512 display clicks onto the front of the device and can be connected to a 4590 to allow for a direct connection to a PC to allow for direct configuration, collecting logged data and event logs.
A real person will answer the phone and deal with your enquiry.
You can also click the button below and fill in our online enquiry form.
Need help with your products or have a question for us on our custom systems? Use the form below to send us a message and our experts will be in touch to help.