Description
Features
- Split core design, simplifies installation
- Ranges available from 0-100 Amps up to 0-1500 Amps
- Linear 0-5vDC output
- Self powered, no external power required
- Rugged plastic housing and Nylon screws, no exposed metal parts
Specifications
Input Current: | AC Current, single phase, 50-400Hz, load factor 0.5 to 1.0 lead or lag. |
Accuracy: | 1% of reading from 10% to 100% of full scale 3% of reading at 5% of full scale 5% of reading at 2% of full scale |
Response Time: | 250 milliseconds, input from 10% to 90% of full scale, 200 amp and higher ranges. |
Output Signal: | Linear 0-5vDC |
Constuction: | ABS potted housing |
Environment: | Indoor Type 1 rating per UL506 |
Operating Temp: | -20 to +55°C |
Dimension: | 1.25 inches (32mm) thick, Length and Width see table below. |
Part No. | Range | Window Size | Length | Width |
SC100A | 0-100 | 0.5″ Square | 2.6″ (66mm) | 2.3″ (59mm) |
SC200A | 0-200 | 1″ Square | 3.3″ (84mm) | 3.0″ (76mm) |
SC500A | 0-500 | 2″ Square | 4.1″ (104mm) | 4.0″ (102mm) |
SC1000A | 0-1000 | 4″ Square | 6.1″ (155mm) | 6.0″ (153mm) |
SC1500A | 0-1500 | 2.5″ Square | 5.4″ (137mm) | 4.7″ (120mm) |