omni instruments | sensors and data acquisition equipment

Sales & Technical Support

Edit Content

OLCT10N-002

OLCT10N Fixed Digital Gas Detector for Methane (CH4), Range 0-4.4% Volume, Accuracy ±1%LEL. Output: RS485 Modbus RTU. Power Supply: 12-30vDC, Consumption 50mA typ. Operating temperature: -20 to +55°C. Life span: 48 Months. Plastic housing, 118 x 157 x 60mm, IP65. Certified to use in ATEX II 3GD zone.

£375.00

Need help finding the right product?

Downloads

OLCT10N Gas Detector

Description

Features

  • Catalytic Sensor Suitable for Hazardous Area Installation
  • RS485 Modbus Output Signal
  • Dust and Humidity Resistant (IP65)
  • Fast and Accurate Response
  • Non-Intrusive Calibration
  • Up to 32 Detectors on Same Digital Line

Specifications

Signal Output: RS485 Modbus RTU
Power Supply: 12 to 30vDC
Power Consumption (24vDC): 50mA
Cable Entries: 2 x M16 Cable Glands, outer diameter 4 to 8mm
Material: ABS, UV and Shocks Resistant
Protection Rating: IP65
Storage Conditions: -50 to +70°C, 20-60%RH.
Storage Duration: 6 Months Maximum
ATEX Certification: EMC according to EN 50270
Explosive Atmospheres : when applicable
Ex II 3 GD
Ex dc ec IIC T4 Gc
Ex tc IIIC T135°C Dc
-20°C<Ta<+55°C

 

Sensor Specifications

Gas Detected: Methane (CH4)
Measuring Range: 0-100% LEL (0-4.4% Volume)
Accuracy: ±1% LEL (0-70% LEL)
Life Expectancy: 48 Months
Response Time: 6 Seconds (T50)
15 Seconds (T90)
Operating Temp Range: -20 to +55°C
Calibration Gas: 2.2% CH4/Air (50% LEL)

 

Dimensional Drawing

We are here to help

Need help with your products or have a question for us on our custom systems? Use the form below to send us a message and our experts will be in touch to help.

Enquire now