Description
IF-96003: Pulse Output Interface for Nemo 96HD/HD+ Series
The IF-96003 module, when combined with meters from the Nemo 96HD/HD+ series, enables the remote repetition of energy count. This module features:
Outputs
- Outputs: 2 independent and insulated outputs.
- Each output can be freely associated with positive or negative active and/or reactive energy counts.
- Maximum Configuration: For each meter (Nemo 96HD/HD+), up to 2 IF-96003 modules can be installed, allowing a total of 4 pulse outputs.
Programmable Parameters for Each Output:
- Associated Energy:
- Positive active energy (EWh+)
- Positive reactive energy (Evarh+)
- Negative active energy (EWh-)
- Negative reactive energy (Evarh-)
- Pulse Weight Options:
- 1 pulse/10Wh, 100Wh, 1kWh, 10kWh, 100kWh, 1MWh, 10MWh
- 1 pulse/10varh, 100varh, 1kvarh, 10kvarh, 100kvarh, 1Mvarh, 10Mvarh
- Pulse Duration Options: 50ms, 100ms, 200ms, 300ms
Outputs Specifications:
- Type: 2 optorelays with potential-free SPST-NO contacts.
- Contact Rating: 110V DC/AC, 50mA.
Auxiliary Supply:
- Rated Burden:
- IF96003 module: ≤ 1VA
- Nemo 96HD/HD+ and IF-96003 interface: ≤ 5VA
- Nemo 96HD/HD+ with 2 IF-96003 interfaces: ≤ 6VA
Insulation (EN61010):
- A.C. voltage test: 2kV r.m.s. value at 50Hz for 1 minute.
- Related Circuits: Measurement input, auxiliary power, output 1, output 2.
Housing:
- Type: Module with a connector for Nemo 96HD/HD+.
- Maximum Depth: 81mm (including module).
- Connections: Screw terminals.
- Terminal Specifications:
- Rigid cable: max. 4.5mm²
- Flexible cable: max. 2.4mm²
- Material: Self-extinguishing polycarbonate.
- Weight: 30 grams.
Firmware Version:
The firmware version that supports the extra module’s function is indicated in the documentation. The version can be updated in the field using an IF-96001 (RS485) or IF-96002 (RS232) communication module with a PC and the necessary software.