Description
DPT-Flow air flow transmitters are designed for building automation systems. These technologically advanced transmitters can measure volume flow, velocity, and static and differential pressure.
The transmitters can be connected directly to the pressure measurement points of a centrifugal fan, providing accurate flow measurement. The user interface enables easy selection of settings according to the selected fan or measurement probe.
Specifications
Power Supply: | 24VDC/VAC (22…26V) |
Power Consumption: | < 1VA |
Pressure Measurement: | 0-1000Pa |
Accuracy (25°C): | Pressure < 125 Pa = ±1% plus ±2 Pa Pressure > 125 Pa = ±1% plus ±1 Pa |
Zero Point Calibration: | Manual with Push Button |
Suitable media: | Dry air and non-aggressive gases |
Output signals: | 0-10/2-10vDC, > 1kΩ 4-20mA, Load 20…500Ω |
Temperature Range: | -20 to +50°C |
Materials Housing: | ABS and PC Plastic |
Cable Gland: | M16 |
Dimensions: | 90 x 75 x 36 mm |
Protection: | IP54 |