Description
Advanced features
- Universal driver for the control of solenoids etc.
- Two hardware versions make it possible to choose either Low (35 mA) or High (60 mA) current output.
- Configuration and monitoring by way of detachable display front (PR 4511/4501).
- Selection of direct or inverted function for each channel via PR 4511/4501 and the possibility of reducing the output current to suit the application.
- Optional monitoring of the output current by way of PR 4511/4501.
- Optional redundant supply via power rail and/or separate supply.
Application
- The device can be mounted in and transmit signals to non-classified area and zone 2.
- Control of ON / OFF solenoids, acoustic alarms and LEDs.
- The 9203A is controlled by an NPN/PNP signal or a switch signal.
- Monitoring of internal error events via the individual status relay and/or a collective electronic signal via the power rail.
- The 9203A has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
Technical characteristics
- 1 green and 2 yellow/red front LEDs indicate operation status and malfunction.
- 2.6 kVAC galvanic isolation between input, output and supply.
Mounting
- The devices can be mounted vertically or horizontally without distance between neighbouring units.
Environmental Conditions
Specifications range | -20°C to +60°C |
Storage temperature | -20°C to +85°C |
Calibration temperature | 20…28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Installation in | Pollution degree 2 & measurement / overvoltage cat. II |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Dimensions (HxWxD) w/ 4501 / 4511 | 109 x 23.5 x 116 / 131 mm |
Weight approx. | 170 g |
Weight incl. 4501 / 4511 (approx.) | 185 g / 270 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13…2.08 mm2Â AWG 26…14 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 : 2007 |
Vibration: 2…13.2 Hz | ±1 mm |
Vibration: 13.2…100 Hz | ±0.7 g |
Common specifications
Supply |
|
Supply voltage | 19.2…31.2 VDC |
Isolation voltage |
|
Test /working: Input to any | 2.6 kVAC / 300 VAC reinforced isolation |
Output 1 to output 2 | 1.5 kVAC / 150 VAC reinforced isolation |
Status relay to supply | 1.5 kVAC / 150 VAC reinforced isolation |
Fuse | 1.25 A SB / 250 VAC |
Max. required power | ≤ 3.5 W (2 channels) |
Programming | Communication enabler 4511 / Programming front 4501 |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE 21, A criterion, burst |
< ±1% of span |
Input specifications
NPN and mechanical switch |
|
Trig level LOW | ≤ 2.0 VDC |
Trig level HIGH | ≥ 4.0 VDC |
Max. external voltage | 28 VDC |
Input impedance | 3.5 kΩ |
PNP |
|
Trig level LOW | ≤ 8.0 VDC |
Trig level HIGH | ≥ 10.0 VDC |
Max. external voltage | 28 VDC |
Input impedance | 3.5 kΩ |
Output specifications
Status relay |
|
Max. voltage | 110 VDC / 125 VAC |
Max. current | 0.3 ADC / 0.5 AAC |
Max. AC power | 62.5 VA / 32 W |
Output ripple | < 40 mVRMS |
Observed authority requirements
EMC | 2014/30/EU |
LVD | 2014/35/EU |
Approvals
UL | UL 61010-1 |
DNV-GL Marine | Stand. f. Certific. No. 2.4 |
SIL | SIL 2 certified & fully assessed acc. to IEC 61508 |