omni instruments | sensors and data acquisition equipment

Sales & Technical Support

Edit Content

6513559

OLC10 fixed gas detector with Wheatstone Bridge output for flammable gases. Range 0-100%LEL for CH4, C3H8, C4H10 or Hydrogen. 3-wire connection, max cable length 300m. Operating Range: -10 to +45°C, 0 to 95%RH. Dimensions: 118 x 126 x 58mm, IP66 ABS housing with M16 gland. ATEX II 3 G – EEx nA IIC T6 Approved.

£190.00

Need help finding the right product?

Downloads

OLC10 Fixed Gas Detector

Description

The OLC10 is designed for detecting the presence of flammable gases in boiler rooms, maintenance rooms and parking structures. The OLC10 is designed to work with the MX15 Flammable and Toxic Gas Alarm system. The MX15 will provide the power supply and alarm outputs for the OLC10. The alarm levels are configurable on the MX15 and has built-in visual and audible alarms. The OLC10s are easy to install, with two screw mounting points on the side of the enclosure.

Features

  • Combustible Gas Monitor
  • Available calibrated for Methane, Propane, Butane or Hydrogen gases.
  • Wheatstone Bridge Output
  • ATEX Approval for use in Hazardous Areas

Specifications

Model: OLC10
Type: Catalytic Bead Sensor
Size: (W x H x D): 118 x 126 x 58mm
Material: ABS
IP Rating: IP65
Expected Lifetime: Catalytic Sensor: > 4 years
Operating Temp: -10 to +45°C
Operating RH: 0 to 95%RH
Operating Pressure: 80 to 120kPa
Accuracy: ±3% LEL (Catalytic)
Response Time: Flammable Gas: <10s
Signal Output: Wheatstone Bridge
Measuring Range: 0-100% LEL
Over Range Protection: Managed by Control Unit
Settings: On Controller
Power Supply: By Control Unit Only
Cabling: 3-Wire, shielded, 1.5mm² core size, max 300m cable length
Approvals: Electro magnetic compatibility according to EN 50270:06 (Type 1)
ATEX II 3 G / Ex nA IIC T6

We are here to help

Need help with your products or have a question for us on our custom systems? Use the form below to send us a message and our experts will be in touch to help.