Description
The DPT-FLOW-1000-AZ-D is ideal for high-precision low flows in HVAC/R building automation systems. This unit provides multi-variable monitoring by measuring volume flow, velocity, and both static and differential pressure. This unit is optimised for versatility, the DPT-FLOW models with the -AZ function are designed for high precision or difficult to access installs that require accurate real-time fan flow data. This specific unit features:
- Integrated Digital Display: The “D” configuration provides an intuitive on-site interface for immediate local monitoring.
- Precision Range: Calibrated for differential pressure of up to 1000 Pa.
- Smart Configuration: The user-friendly interface allows for rapid commissioning, with pre-set parameters for various fan manufacturers and in-duct measurement probes.
- Auto-Zeroing: The -AZ Models include an automatic zeroing function, which zeroes the pressure measurement every 10 minutes.
Applications
- Control the ventilation system via connected EC controller, frequency inverter or other control unit with 0-10 V power supply.
- Monitoring air volume flow or pressure directly on air handling unit
- Ideal sensors for LEED (Leadership in Energy and Environmental Design) projects
- Can be used to monitor VAV (Variable Area Volume) Boxes in HVAC Systems
Features
- Connect directly on fan or ventilation unit
- Output signals for differential pressure and air volume flow
- Auto-Zeroing is an internal automated valve that re-calibrates the sensor every 10 minutes.
- Includes a 5 Year Warranty
Specifications
| Power Supply: | 24VDC/VAC (22…26V) |
| Power Consumption: | < 1VA |
| Pressure Measurement: | 100-1000Pa |
| Accuracy (25°C): | Pressure < 125 Pa = ±1% plus ±2 Pa Pressure > 125 Pa = ±1% plus ±1 Pa |
| Zero Point Calibration: | Automatic Zeroing. Zeroes the pressure measurement every 10 minutes to eliminate any zero point drift. |
| Suitable media: | Dry air and non-aggressive gases |
| Output signals: | 0-10/2-10vDC, > 1kΩ 4-20mA, Load 20…500Ω |
| Temperature Range: | -5 to +50°C |
| Materials Housing: | ABS and PC Plastic |
| Cable Gland: | M16 |
| Dimensions: | 90 x 95 x 36 mm |
| Protection: | IP54 |
Auto-Zeroing Technology
High-performance HVAC systems rely on stable data. Over time, standard differential pressure sensors can “drift” due to environmental changes, leading to inaccurate flow readings and wasted fan energy.
- Automatic Calibration: The Autozero (-AZ) models feature an internal solenoid valve that periodically re-calibrates the zero point (every 10 minutes).
- Reduced Site Visits: Eliminates the need for manual annual re-zeroing by a technician.
- Critical Environments: Recommended for hospitals, cleanrooms, and high-ceiling AHUs where manual access is difficult or costly.
- Energy ROI: Ensures your Q = k × √ΔP calculation remains 100% accurate, preventing Variable Frequency Drives (VFDs) from over-running due to sensor error.