Description
The MX16 controller comes pre-configured from the factory to accept a 4-20mA signal from a suitable Oxygen (O2) gas detector. The MX16 can provide a 24vDC supply to the gas detector.
Features
- Single channel gas controller
- Low Cost and Easy to Install
- Integrated Relays
- Easy to read large graphic and multi-language LCD back-lit display
- Soft-touch Keys for Embedded Menus
Applications
- Monitoring levels of Oxygen in enclosed areas.
- Gas Leaks in Boiler Rooms
- Gas Releases in Battery Charging Areas
- Water Water Treatment Plants
- Petrochemical Industry
- Laboratories
Specifications
General Specifications
| Dimensions: | 265 x 266 x 96mm |
| Ingress protection | IP55 |
| Cable entries:
|
3 M16 cable glands, 4 to 8 mm² (8 to 11 AWG) outer diameter cable 2 M20 cable glands, 6 to 12 mm² (7 to 9 AWG) outer diameter cable |
| Display:
|
LCD back-lit display + smart keys Display in grayscale in case of fault Bar graph with alarm threshold |
| Visual indicators: | 6 LEDs, 5 LEDs for Detector Status Line, 1 LED fault indicator and 1 LED Power Condition |
| Buttons: | 5 smart keys, 1 audible alarm accept/reset button |
| Operating Environment: | Temp: -20°C to +50°C, Humidity 5 – 95%RH |
| Power Supply: | 100-240vAC 50-60 Hz (35W) |
| Consumption: | 250 mA max (without captor) |
Alarms
| Per channel: |
2 alarm levels (A1, A2) + 1 Fault |
| Programmable thresholds: | Instantaneous or averaged values, falling alarms, manual or automatic acknowledgement |
| On-board relays:
|
2 alarm relays 1 fault relay (non-configurable) Dry contact relay Dry Contact Relay, RCT, 250vAC, 5A |
The MX16 is delivered alone and does not include a detector. WCDCOM16 Software will allow for re-configuration for 4-20mA or Digital Inputs.The MX16 can be used with the OLCT 10N Oâ‚‚, CO, COâ‚‚, CHâ‚„, LPG and Hâ‚‚ digital sensor series or any other Oâ‚‚, CO, COâ‚‚, CHâ‚„, LPG and Hâ‚‚ analog sensor.
Pre-Configured for Gas Detector
| Gas Detected: | O2 (Oxygen) |
| Range: | 0-30% Volume (-40 to +50°C) |
| Power Supply: |
24vDC |
Gas Detector Connection Diagram
Please ensure that local regulations are adhered to when installing detectors to the MX16 control panel, with suitable circuit breakers or barriers for the installation.