Description
The SharpEye 40/40C-M Multispectrum Quad-Sense flame detector is part of the leading, next generation SharpEye 40/40 series. Featuring enhanced performance, advanced long distance detection of hydrogen and hydrocarbon fires, fast detection in under 5 seconds and strengthened reliability, the SharpEye 40/40C-M is based on proven triple infrared (IR3) technology, ensuring highest sensitivity with proven immunity to false alarms
Features and Benefits
Multi-Spectrum Quad-Sense™ flame detector – integrating four infrared (IR) sensors to further improve differentiation of flame sources from non-flame background radiation.
- Advanced long distance detection of hydrogen and hydrocarbon-based fuel and gas fires at up to 215 ft (65 m)
- Fast detection, under 5 seconds
- Proven false alarm immunity
- Unparalleled reliability – 150,000 hours MTBF
- Best in class temperature range: -40°F (-40 °C) to 167 °F (75 °C)
- Enhanced durability backed up by three-year warranty
- Five sensitivity levels, adapting to any application
- Innovative infrared built-in test (BIT) – continuously validating the optical integrity and the electronic circuitry
- Multiple output options for maximum compatibility with standard infrastructures
- Plug and play – factory calibrated for immediate use in any fire detection system
- Universal wiring option for fast ordering process
- Heated optics for impeccable performance in challenging environmental conditions
- Worldwide and regionally certified for hazardous areas
- Performance and reliability approved by recognizable certification bodies
- SIL3 compatible
- Internal log event recorder to analyze past events
Applications
- Oil & gas onshore and offshore installations and pipelines
- Hydrogenation (petroleum refining, food processing, and chemical)
- Chemical and petrochemical plants
- Storage tank farms
- Fuel and gas processing and storage facilities
- Power generation
- Explosives and munitions
- Fertilizer plants
- Automotive industry
- Vehicle battery charging stations
- Hydroxyl production and storage
- Aerospace industry
- Pharmaceutical industry
- Printing
- Hazardous materials storage areas
- Food processing
- Light industrial
Specifications
General Specifications
Detection Response Time | Standard Response: | Typically <5 seconds |
Sensitivity Ranges | 5 Sensitivity Ranges for 1ft² (0.1m²) n-Heptane Pan Fire | |
Field of View | For Hydrogen: | Horizontal: 90°, Vertical: 90°. |
For other fuel: | Horizontal: 80°, Vertical: 80°. | |
Temperature Range | Operating Storage Temperature: -40 to 167F (-40 to +75°C) | |
Humidity | Non-condensing Relative Humidity up to 100% |
Electrical Specifications
Power Supply | 24vDC Nominal (18-32vDC) |
Power Consumption
|
Standby: Maximum 3W (8W with heated window) Alarm: Maximum 4.2W (9.6W with heated window) |
Electrical Input Protection | According to EN 50130 |
Electromagnetic Compatibility | EMI/RFI Protected to EN61000-6-3 and EN50130 |
Electrical Interference | The detector includes 17 terminals, one wiring option |
Outputs
Relays | Alarm, Fault, and Auxiliary SPST volt-free contacts rated 2A at 30vDC |
Analogue Output
|
Analogue Port Malfunction: 0V (<0.5V) Normal: 2V ±0.3V Alarm/Explosion: 5V ±0.3V |
0-20mA (Stepped)
|
Fault: 0 ±1mA Built-in Test (BIT) Fault: 2mA ± 0.3mA Normal: 4mA ± 0.3mA Warning: 16mA ± 0.3mA Alarm: 0mA ±0.3mA |
HART Protocol
|
HART Communication on the 0-20 Analogue Current (FSK) used for maintenance, configuration changes, and asset management, available in mA source output wiring option |
RS485 | RS485 Modbus compatible communications link that can be used in computer controlled installations |
Mechanical Specifications
Enclosure Options: |
Heavy Duty Copper Free Aluminium (less than 1%), Polyurethane Painted |
Mounting: | Electropolished Stainless Steel 316 |
Dimensions: | Detector: 4″ x 4.6″ x 6.18″ (100.6 x 117 x 155mm) |
Weight:
|
Detector Aluminium: 2.8lb (1.3Kg) Tilt Mount: 2.5lb (1.1Kg) |
Water and Dust: | IP66 and IP68 per EN60529 NEMA 250 6P |
Approvals
ATEX and IECEx
|
Ex II 2GD Ex db eb IIC T4 Gb Ex tb IIIC T110 °C Db Ta = -40 °C to +75 °C IP66/IP68 |
FM/FMC/CSA
|
Class I Division 1, Groups B, C, and D, T4 Class II/III Division 1, Groups E, F, and G, T4 Class I, Division 2, Groups B, C, and D, T4 Ta = -40 °C to +75 °C Type 6P; IP 66/68 6.6 ft (2 m) for 45 minutes |
TR CU (EAC) | 1Ex d e IIC T4 Gb Ex tb IIIC T110 °C Db Ta = -40 °C to +75 °C IP66/IP68 |
IN METRO | Pending |