Description
Applications
- Linearised temperature measurement with PT100 or Ni100 sensor.
- Conversion of linear resistance change to standard analogue current / voltage signal from e.g. valves or linear movements with attached potentiometer.
- Signal simulator via externally mounted 10-turn potentiometer.
Features
- Programmable via PC
- Input for Pt100, Ni100 or Ohm
- Linearised analogue output
- 24 VDC supply
- Single channel version
- DIN rail mounting
Configuration
The transmitter may be configured to the requested signal type by means of a DOS-based PC with the configuration program PReset 5000 and the communications unit Loop Link. The configuration of the transmitter may be done without connection of supply voltage as the communications unit supplies the required power. The supply voltage is 24VDC with the same reference point for supply, input and output ground. The sensor connection is always a 3-wire connection with cable compensation for up to 50 Ω in each
wire. If a 2-wire connection is requested, pins 43 and 42 (channel 1) must be short-circuited in the connection plug (no cable compensation). Sensor error detection is as standard set to Upscale, Downscale or entered to special output value.
Options
Type | Channels |
5102 | A: Single |
The 5102 Adjustable R/I Transmitter was discontinued from 30th June 2015.
Recommended products, which can replace the 5102 are available on the list below. The product can be replaced by the 3102 (PT100) or 4114 (Linear Resistance/Potm).