Description
On batteries the METEON consumes 2.5 mA, with back light on this is 12 mA. Each additional SMP adds 7 mA, So logging of one analog and one smart sensor consumes 9.5 mA. With Alkaline batteries of 2200 mAh this means a lifetime of approximately 230 hour. When the METEON is powered with 12VDC this can be transferred to the Modbus sensors as well.
Features
- Live irradiance display and logging
- Modbus® and analog instruments
- Panel temperature sensor input
- kWh energy pulse counter
- Power and configure Smart sensors
- Comparison mode for testing
- User-friendly Windows™ software
- Long battery life (50 days with 2 AA batteries)
Specifications
Measurement Requirements | Specification |
Analog mV range full scale | Suitable for all Kipp & Zonen radiometers |
Analog resolution | 0.1W |
Basic accuracy after calibration | 0.1% |
Temperature sensitivity over full temperature range | < 0.5% |
Offset drift over full temp range | < 3µV |
Input circuit | >2M?Ý 470 nF |
Sampling / filter | 1s, 50 / 60 Hz filtering |
Logging | 1,2,5… s, min, h, aver, min, max |
Modbus input | 5 x Smart Sensor |
RTC accuracy | 5 min /y |
Logging | Internal memory |
Functionality | |
Display, logging | Up to 7 sensors |
Meteon RS485 port setting | Set communication parameters |
Modbus / comm. setting | Set address & comm. (per 1 dev) |
Comparison & logging | 2 radiation sensors |
RS485 to USB | Transparent mode |
Design | |
PC / Calibration | Via mini USB connector |
Sensor connectors | Wago / Phoenix |
LCD | Graphic, 8 lines of text, back light Good sunlight readability |
Keyboard | Up, Down, Left, Right, OK, On/Off, Back Light |
Batteries | 5 x AA type |
Battery life | >3 days, 3 sensors logging |
DC connector | input for DC power supply 10 – 24 V (± 10%) |
Connected instruments | |
Analogue | CM, CMP, CUV, SP-Lite, PQS |
Modbus | SMP, SUV, SGR, SHP, PR1, PH1, RT1, M&T |
Communication | USB,transparent mode RS-485 to USB |
USB | Mini USB, opto isolated |
RS485 | 70V tolerant TVS protection |
PC Software | Dedicated PC software to: Visualize – Display actual sensor values – Comparison data – Data graph Calibration of METEON 2.0 Export of csv data |
Delivery | METEON 2.0, Carrying case with Room for 1 pyranometer Calibration certificate, USB cable, Connectors for inputs |
Environment/Testing | |
Operating Temperature Range | -10 to +40°C, <95%RH Non-Condensing |
Storage Temperature Range | -20 to +50°C, <95%RH Non-Condensing |
Approvals | CE / FCC / RoHS |