The PR Electronics 9400 Power Rail combines DIN rail mounting with shared DC power distribution for compatible 3000 and 9000 series modules. Rear contacts connect each compatible device to the rail’s conductors, reducing individual supply wiring and simplifying installation, expansion and maintenance. Sensor inputs and signal outputs remain connected through each module’s terminals.
Available in different lengths, with 7.5 mm or 15 mm deep profiles, the power rail suits installations ranging from small groups of signal conditioners to larger control panels. An external DC power supply is required.
For compatible 3000 series devices, an external 24 V DC supply can be connected to one module’s supply terminals to energise other devices on the same rail. This arrangement uses a 0.4 A protective fuse.
For larger installations, the 3405 Power Connector provides a dedicated feed connection rated up to 2.5 A. The 9410 Power Control Unit supports feeds up to 4 A and adds supply monitoring, backup supply connections and collective fault indication from supported modules.
The following tables show indicative device capacities for different feed arrangements.
P100% uses the full maximum required power stated in the device datasheet. The supplied guidance describes nominal operating conditions such as a 24 V supply, 60°C ambient temperature, 600 Ω load and 20 mA output.
P70% uses 70% of that maximum power as an engineering estimate for installations where devices operate below the stated maximum demand. This assumption should be checked against the actual operating conditions.
| Power calculation basis | Compatible PR converter as power feed-in | 3405 power feed-in | 9410 power feed-in |
| P70% | Up to 21 devices | Up to 131 devices | Up to 210 devices |
| P100% | Up to 14 devices | Up to 92 devices | Up to 147 devices |
These figures are based on the PR 3103, which has the lowest power consumption among the 3000 series power rail devices. Other models, or combinations of models, may allow fewer devices. Modules can be arranged on horizontal or vertical rails, subject to their installation requirements.
| Power calculation basis | 9410 power feed-in |
| P70% | Up to 150 devices |
| P100% | Up to 120 devices |
These figures provide planning guidance. The final capacity depends on the selected devices, their operating loads and the available supply capacity.
Check power rail compatibility for each exact model and calculate the combined power demand before selecting the feed arrangement. Terminal-powered -N versions, such as the 3225A-N and 3225B-N, require direct supply wiring. Allow sufficient capacity for the installed equipment and any planned expansion.
The PR Electronics 9400 series 15 mm Power Rail provides mounting and shared DC power distribution for compatible 3000 and 9000 series modules. Its 35 × 15 mm profile reduces individual supply wiring, with lengths of 250, 500, 750 and 1,000 mm available. Each rail includes a protective cover and two end covers, with power supplied through a suitable feed device connected to an external DC supply.
The PR Electronics 9400 series 7.5 mm Power Rail provides mounting and shared DC power distribution for compatible 3000 and 9000 series modules. Its compact 35 × 7.5 mm profile reduces individual supply wiring, with lengths of 250, 500 and 750 mm available. Each rail includes a protective cover and two end covers, with power supplied through a suitable feed device connected to an external DC supply.
The PR 3405 Power Connector connects an external DC supply to the PR 9400 Power Rail, distributing power to compatible modules without separate supply wiring to each device. Its slim 6.1 mm housing saves panel space and supports a feed current of up to 2.5 A. The 3405 requires an external power supply; it does not convert mains voltage to DC.
The PR 9410 Power Control Unit distributes power from an external DC supply to compatible modules on the PR 9400 Power Rail. It supports a feed current of up to 4 A, with connections for primary and backup supplies. Front LEDs indicate supply and alarm status, while a status relay provides collective fault indication from supported modules. The 9410 requires an external DC power supply.
A real person will answer the phone and deal with your enquiry.
You can also click the button below and fill in our online enquiry form.
Need help with your products or have a question for us on our custom systems? Use the form below to send us a message and our experts will be in touch to help.