The PR3225 is a compact universal frequency converter for connecting pulse-output sensors to industrial monitoring and control equipment. It accepts supported NAMUR, NPN, PNP, tacho, TTL, S0 and contact signals, with analogue or relay outputs depending on the version. Its 6.1 mm DIN rail housing suits control panels where space is limited.
Analogue output versions convert the measured frequency into a configurable current or voltage signal. This allows compatible flow meters and speed sensors to connect to PLCs, indicators and data acquisition equipment with analogue inputs.
Available ranges include 4-20 mA and 0-10 V. Input and output scaling establish the relationship between the sensor frequency and the reported process value.
Relay output versions provide setpoint, window and latch functions. These allow a switching response when a measurement reaches a configured limit or moves outside a permitted range.
For example, a compatible speed sensor can provide the input for low-speed monitoring, while a suitable pulse-output flow meter can support a flow-limit indication. The sensor characteristics and relay settings must match the application.
Programmable trigger levels help match the input to supported signals. A configurable 5–17 V supply can power compatible sensors within its current limit.
The 3225 measures frequencies up to 100 kHz, subject to configuration. An input filter is available for appropriate low-frequency signals, with a reduced frequency limit when enabled. Three-port galvanic isolation separates the input, output and supply circuits.
DIP switches provide configuration for selectable settings. A compatible PR 4500-series interface, connected through the PR 4590 ConfigMate, provides access to configuration, monitoring and diagnostics.
Two-point process calibration and process-value simulation support commissioning and checks of connected equipment.
The 3225 operates from a 16.8–31.2 vDC supply and can be powered individually or through a compatible PR power rail. Select the output version to match the receiving equipment, then confirm the sensor signal, frequency range, supply and installation requirements.
| Type | Version | Terminals |
| 3225 | A: Universal Frequency Converter, Analogue Output B: Universal Frequency Converter, Alarm Relay Output |
-: With Power Rail Connector/Terminals N: Supplied with Terminals |
Applications
Frequently Asked Questions
PR 3225A Slim Series Universal Converter suitable for use in Hazardous Areas. Frequency Input: 0.001Hz to 100kHz. Output: 1 Analogue (Current: 0-20, 4-20, ±10mA, or ±20mA; Voltage: 0-5, 1-5, 0-10, 2-10, ±5, ±10vDC), Power and Off). Power Supply: 24vDC ±30%, via power rail or terminals. 6mm Slimline housing.
PR 3225B Slim Series Universal Converter suitable for use in Hazardous Areas. Frequency Input: 0.001Hz to 100kHz. Output: 1 Relay Output (Setpoint, Window, Sensor error, Latch, Power and Off). Power Supply: 24vDC ±30%, via power rail or terminals. 6mm Slimline housing.
PR 3225A-N Slim Series Universal Converter suitable for use in Hazardous Areas. Frequency Input: 0.001Hz to 100kHz. Output: 1 Analogue (Current: 0-20, 4-20, ±10mA, or ±20mA; Voltage: 0-5, 1-5, 0-10, 2-10, ±5, ±10vDC). Power Supply: 24vDC ±30%, via terminals only. 6mm Slimline housing.
PR 3225B Slim Series Universal Converter suitable for use in Hazardous Areas. Frequency Input: 0.001Hz to 100kHz. Output: 1 Relay Output (Setpoint, Window, Sensor error, Latch, Power and Off). Power Supply: 24vDC ±30%, via terminals only. 6mm Slimline housing.